Connectors & Wiring — Cheat Sheet

Wire sizing, voltage drop, crimping, shielding, strain relief and IP sealing.

Wire sizing

AWG diameterd(mm) = 0.127 × 92^((36−n)/39)
Area stepeach −3 AWG ≈ doubles area
Copper resistanceR ≈ 17.24 / area(mm²) Ω/km
Voltage drop (DC)V = 2 · I · ρ · L / A (round trip)
Target drop≤ 3% signal/branch, ≤ 5% total

Current & derating

Free airsingle conductor carries the most
Bundledderate — mutual heating
Connectorderate ~50% when all contacts energized
Fuse rating≈ 1.25 × continuous current
Fuse energyI²t must exceed the inrush let-through

Termination

Crimpgas-tight, correct die — stronger than solder for vibration
Solder + vibrationwicking makes a stiff spot that fatigues
Strain reliefalways — the joint must never carry load
Bend radius≥ 5–10× cable OD
Service loopleave slack for one re-termination

Shielding & sealing

Shield groundONE end only for signals (avoids ground loops)
Twisted pairrejects magnetic pickup; pair the return with the signal
Separationroute power and signal apart, cross at 90°
IP ratingfirst digit solids, second liquids (IEC 60529)
Backshellstrain relief + shield termination in one

Formula reference — verify against the governing standard. Not a substitute for engineering judgment.