Psychrometrics & HVAC — Cheat Sheet

Moist-air relations, coil loads, duct and ventilation sizing, refrigeration metrics.

Moist air basics

Humidity ratioW = 0.622 p_w / (p − p_w) [kg/kg dry air]
Relative humidityφ = p_w / p_ws
Enthalpyh = 1.006t + W(2501 + 1.86t) [kJ/kg dry air]
Specific volumev = 0.287(t+273.15)(1+1.608W) / p [m³/kg dry air]
Key pointh and v are per kg of DRY air, not per kg of mixture

The three temperatures

Dry bulbWhat a thermometer reads
Dew pointCool at constant W until saturated — predicts condensation
Wet bulbEvaporatively cooled; sits between the other two
At 100% RHAll three are equal
Heating airW and dew point unchanged; RH falls (why winter feels dry)

Coil loads

SensibleQ_s = ṁ_da · c_p · Δt
LatentQ_l = ṁ_da · ΔW · h_fg
TotalQ_t = ṁ_da · Δh
Sensible heat ratioSHR = Q_s / Q_t; comfort cooling 0.65–0.80
Shortcut (SI, std air)Q_s(kW) ≈ 1.23 × L/s × Δt

Duct sizing

Equal frictionSize everything to one Pa/m; 0.8–1.0 Pa/m typical
Velocity pressurep_v = ½ρv² (60 Pa at 10 m/s)
Equivalent roundD_e = 1.30(ab)^0.625 / (a+b)^0.25
Velocity limitsbranch < 5 m/s, main 8–10 m/s — noise governs
Aspect ratioKeep under 4:1

Ventilation (ASHRAE 62.1)

Breathing zoneV_bz = R_p·P_z + R_a·A_z
Zone outdoor airV_oz = V_bz / E_z
OfficeR_p = 2.5 L/s·person, R_a = 0.3 L/s·m²
CO₂ rise≈650 ppm at 8 L/s per person
NoteE_z < 1 raises what you SUPPLY, not what arrives

Refrigeration

COPcooling capacity / power input
EEREER = 3.412 × COP
kW per tonkW/ton = 12 / EER = 3.517 / COP
1 ton12 000 BTU/h = 3.517 kW
Carnot limitCOP_max = T_e / (T_c − T_e) [kelvin]
Heat rejectedcapacity + compressor power

Building envelope

Assembly RR = Σ(t/k) + R_si + R_se
Surface films (ISO 6946)R_si = 0.13, R_se = 0.04 m²·K/W
U-valueU = 1/R (lower is better)
Unit trapR(imperial) = 5.678 × R(SI)
Inside surface tempT_si = T_i − U·ΔT·R_si
Mould riskf_Rsi = (T_si − T_o)/ΔT; below ~0.75 is a problem

Formula reference — verify against the governing standard. Not a substitute for engineering judgment.