Refrigeration & COP

Every efficiency metric in refrigeration is the same number wearing a different hat — COP, EER and kW/ton all describe one ratio. What actually sets the ceiling is the temperature lift: the gap between evaporating and condensing. Drop the condensing temperature a few degrees and the whole machine gets cheaper to run, which is why condenser fouling costs so much.

COP (cooling)
EER
kW per ton
Capacity
Carnot COP
Second-law efficiency
Temperature lift
Heat rejected

Carnot uses the refrigerant’s saturation temperatures, not the air or water temperatures either side — the approach across each heat exchanger is part of what a real machine loses. A well-designed chiller runs roughly 40–60% of Carnot; well under that usually means excessive lift, fouling, or a badly matched compressor. Rated efficiency figures such as IPLV and SEER are seasonal averages and are not comparable to a single-point COP.

Design-stage estimates. A real project needs a full load calculation to the ASHRAE/CIBSE procedure, and ventilation rates are code-mandated — check the standard and jurisdiction that apply to your building. A helper, not a substitute for engineering judgment.